Home > Notice of Letting > Contract Detail

November 08, 2024 Letting 12:00 PM
05A-AU074

Bulletin Description

Rehabilitate Airfield Lighting Vault and Replace Vault Generator
Region District DBE % VBP % Federal Project #
1 1 0.00 0.00 317SBGP184
County(s) IL Project # Airport Sponsor City
  • Kane
ARR 4915 Aurora Municipal City of Aurora Sugar Grove
Contract Specifics
The time limit to award this item has been changed from 45 days to 90 days after the scheduled letting.
61 Calendar Days
WARNING:  FAA Buy American Preference provisions apply to this contract.  Failure to submit a “Certification of Compliance with FAA Buy American Preference – Construction Projects” form in accordance with the bidding procedures set forth in the proposal document (Appendix A4 BUY AMERICAN PREFERENCE) will result in the bid being declared non-responsive.
No More Contract Specifics

Ask Subscribe Questions and Answers (3 Submitted / 3 Answered ) Questions not accepted as of October 29, 2024 04:30 PM.

  • The specs indicate that one dry contact output is required for the beacon at the tower cab. The plans indicate there’s a transceiver & interface panel for remote beacon control; they also show an interface node on the vault network. Please confirm: will the ALCMS be supplying a single dry contact output? Is it possible to get monitoring feedback of the beacon through a current operated switch? Where will the beacon interface be (tower or vault)?
    The ALCMS will not be supplying a single dry contact output and monitoring feedback of the beacon will not be getting through a current operated switch. The Beacon control and interface will be in the Vault. A complete control and monitoring of Beacon circuit at the Vault is required as shown on ALCMS Block Diagram on Sheet 13. (10/21/2024)

  • The plan notes indicate a transceiver & interface panel for the ATS/generator, but the ATS/generator interface is also shown as a DCME on the vault network. Please advise how the ATS/generator are to be controlled and monitored.
    The ATS/Generator control and interface will be in the Generator enclosure. A complete control and monitoring of ATS & Generator at the Generator is required as shown on ALCMS Block Diagram on Sheet 13. (10/17/2024)

  • The plan notes indicate a transceiver & interface panel for the REILS & windcone, but the REILS & windcone Interfaces are also shown as DCMEs on the vault network. Please advise how the REILS & windcone(s) are to be controlled and whether they can / shall be monitored such as with a current operated switch.
    The REIL’s & Windcone control and interface will be in the Vault. A complete control and monitoring of REIL’s & Windcone circuits at the Vault is required as shown on ALCMS Block Diagram on Sheet 13. (10/17/2024)

Authorized Bidders

  • 2475 Hecker and Company, Inc.
    250 Industrial Lane
    Wheeling, IL 60090
    Phone: (847) 459-9222 Fax: (847) 459-9250 Email: dan@heckerco.com
    $1,257,600.00 is within a reasonable approximation of the Estimate

  • 1320 D. Construction, Inc.
    1488 So. Broadway
    Coal City, IL 60416
    Phone: (815) 634-2555 Fax: (815) 634-8748 Email: bids@dconstruction.com

  • 3011 J. Ranck Electric, Inc.
    1993 Gover Parkway
    MT. Pleasant, MI 48858
    Phone: (989) 775-7393 Fax: (989) 775-7393 Email: ajranck@jranck.com
    $1,628,250.00

  • 6388 William T. Connelly Inc. dba Connelly Electric Company
    40 S. Addison Rd.
    Suite 100
    Addison, IL 60101
    Phone: No Record Fax: No Record Email: No Record
    $1,475,000.00

Non Bidders

  • No requests received
Pay Item # UOM Description Type Quantity Unit Price
AR109210 L SUM VAULT MODIFICATIONS Base items 1.000
AR109311 EACH 7.5 KW REGULATOR, STYLE 1 Base items 2.000
AR109331 EACH 15 KW REGULATOR, STYLE 1 Base items 1.000
AR109341 EACH 20 KW REGULATOR, STYLE 1 Base items 1.000
AR109361 EACH 30 KW REGULATOR, STYLE 1 Base items 4.000
AR109362 EACH 30 KW REGULATOR, STYLE 2 Base items 4.000
AR109810 EACH GENERATOR Base items 1.000
AR109903 EACH REMOVE REGULATOR Base items 16.000
AR109908 L SUM REMOVE GENERATOR Base items 1.000
AR150510 L SUM ENGINEER'S FIELD OFFICE Base items 1.000
AR150520 L SUM MOBILIZATION Base items 1.000
AR800192 L SUM INSTALL ALCMS L-890 Base items 1.000
No More Pay Items

The contract details above are for informational purposes only until the Plans and Special Provisions are posted on this web page. If an addendum is posted, the contract details above may be revised. Please continue to check for addenda.